Transformer model extension for variation of additional losses with frequency

  • Authors:
  • Marius Constantin Popescu;Gheorghe Manolea;Cornelia Aida Bulucea;Niculae Boteanu;Liliana Perescu-Popescu;Ioan Ovidiu Muntean

  • Affiliations:
  • Faculty of Electromechanical and Environmental Engineering, University of Craiova, Romania;Faculty of Electromechanical and Environmental Engineering, University of Craiova, Romania;Faculty of Electromechanical and Environmental Engineering, University of Craiova, Romania;Faculty of Electromechanical and Environmental Engineering, University of Craiova, Romania;Charles Logier College Craiova, Romania;Faculty of Mechanical and Electrical Engineering, University of Petrosani, Romania

  • Venue:
  • ACMOS'09 Proceedings of the 11th WSEAS international conference on Automatic control, modelling and simulation
  • Year:
  • 2009

Quantified Score

Hi-index 0.00

Visualization

Abstract

This article begins with a study of transformer additional losses due to the presence of non-sinusoidal loads, presents existing models to represent these losses and proposes an original model. Consequent increment in transformer loss of life is studied by means of a sensitivity analysis of the model to transformer rated power, load amplitude, thermal inertia, profiles correlation and harmonic spectrum content.